Kitchen fire suppression in New York: code and service

  1. Pick what you need and give your kitchen's ZIP code.
  2. Each service goes to the number of local companies you choose, from one to five. We check licenses where the law requires one and email you their names.
  3. You talk with them and decide. You hire and pay the company directly.
Get a quote

Facts checked 2026-11-15.

Section 904.14 of the 2025 Fire Code of New York State governs the automatic fire-extinguishing system over a commercial cooking line. It sets what kind of system is acceptable, where the manual pull goes and how often the system is serviced.

1. What the Fire Code requires

The system must be a type recognized for commercial cooking equipment and exhaust. Pre-engineered dry and wet chemical systems are tested to UL 300. The system is installed under the Fire Code, NFPA 96, its listing and the maker's instructions.

The code names a standard for each kind of system:

System typeStandard
Wet chemicalNFPA 17A
Dry chemicalNFPA 17
Carbon dioxideNFPA 12
SprinklersNFPA 13
Water mistNFPA 750
FoamNFPA 11

The Fire Code's list of referenced standards shows NFPA 17A in its 2021 edition and NFPA 96 in its 2024 edition.

Duct CylinderWet chemical agent NozzlesOver each appliance, in thehood plenum and the duct Fusible linksMelt in a fire and set offthe system on their own FryerGriddleRange Gas shutoff valve: closes when the system goes off Pull stationSet it off by hand, on theway out of the kitchen
The parts of a kitchen suppression system. Nozzle count and placement come from the maker's listing for your line.

2. Where the manual pull goes

Section 904.14.1 puts the manual actuation device at or near a means of egress from the cooking area. It sits at least 10 feet and no more than 20 feet from the kitchen exhaust system, 42 to 48 inches above the floor, and it must clearly identify the hazard it protects.

A local company can take it from here. One form, free for restaurants.

Get a quote

3. Service and records

Section 904.14.5.2 says systems protecting commercial cooking are serviced at least every six months and after any activation. The inspection is done by qualified individuals, and a certificate of inspection goes to the fire code official when the work is done.

Section 904.14.5.3 covers parts that wear out. Fusible links and automatic sprinkler heads are replaced every year, except frangible bulbs. Other devices follow the maker's instructions.

A red suppression cylinder mounted under a hood beside a True cooler
A suppression cylinder beside a True cooler.

4. When the kitchen changes

Section 904.14.5.1 applies when the cooking media, the position of the equipment or the equipment itself changes in an existing cooking system. The extinguishing system then has to be brought up to sections 904.14 through 904.14.4. New equipment or a moved range can trigger this, so tell the company before you rearrange the line.

5. Who may service the system

The Fire Code says "qualified individuals" and names no license. We found no statewide license for kitchen suppression servicers. Suffolk County does license technicians and companies that service or install automatic fire-extinguishing systems, through its Fire Extinguisher Licensing Board; the Suffolk County page has the details. For any other county, ask the local fire code official what proof of qualification the office accepts.

Two Ansul suppression cylinders and their release in the cabinet of an Accurex hood
Ansul cylinders in the cabinet of an Accurex hood.

6. Where plans go

Local building and code offices review plans and inspect the work, and the fire code official receives the inspection certificate. Ask the code office in your town or city which office handles fire protection plans for a kitchen. The hoods and exhaust guide explains how the hood and its suppression system fit together.

7. Checking a company before you hire

  1. Ask what the company is qualified to service and what proof it can show.
  2. Ask whether it sends the certificate of inspection to the fire code official.
  3. If your kitchen is in Suffolk County, ask for the technician's county license and the company's certificate of registration.

Use the form to describe the kitchen and the job, and the request goes to the number of local companies you choose (one to five).

Questions

How often must a New York kitchen suppression system be serviced?

At least every six months and after any activation, according to Fire Code section 904.14.5.2. The inspection is by qualified individuals.

Where does the manual pull station go?

At or near a means of egress from the cooking area, 10 to 20 feet from the exhaust system and 42 to 48 inches above the floor, under section 904.14.1.

How often are fusible links replaced?

Every year under section 904.14.5.3. Frangible bulbs are excepted, and other devices follow the maker's instructions.

Does New York license suppression system companies?

We found no statewide license. Suffolk County has its own licensing board, and other places may set local rules, so ask your fire code official.

Sources

  1. 2025 Fire Code of New York State (DOS PDF)
  2. DOS notice of adoption, 2025 Uniform Code
  3. 19 NYCRR Part 1225
  4. Suffolk County Fire Extinguisher Licensing Board
  5. 2025 Mechanical Code of New York State (DOS PDF)